Power Supply
Input Power Voltage Range
12VDC Models: 10.4-14.4V
24VDC Models: 20.4-28.8V
110/220VAC: 85-265VAC
Power Consumption
12VDC: 12-point, 150mA
20-point: 150mA
24VDC: 12-point, 90mA
20-point: 150mA
100-240VAC: 90mA
Programming
Program cable EDRS232 or EDUSB upload/download, monitor
Programming languages Function Block
Program Memory 300 Lines or 260 Function Blocks
Programming storage media Flash
Execution Speed 10ms/cycle
Built-in HMI
Customizable screens 31 (H coils)
LCD Display 4 lines x 16 characters
Function Keys 6, 4 user-defined (Z inputs)
Auxiliary
Coils
Maximum Number 126 (63 M-coils, 63 N-coils)
Timers
Maximum Number 31 T-coils
Timing ranges 0.01s–9999min
Counters
Maximum Number 31 C-coils
Highest count 999999
RTC
(Real Time Clock)
Number available 31 R-coils
Resolution 1 min
Time span available week, year, month, day, hour, min
Daylight Savings feature Yes
Power off RTC retention 240 hours
Compare Instructions (Analog, Timer, or Counter Values)
Number available 31 G-coils
Compare functions EQ, LT, GT, LE, GE, NE
Data
Multiplexer Instructions
Number
available 15 (MX Coils)
Resolution 2-bit, 4 data registers
Data
Registers
Number
available 240 (DR Coils, 16-bit)
Shift
Instruction
Number
available 1 8-bit (S Coil)
Analog Ramp Instructions
Number
available 31 (AR Coils)
Environmental
Enclosure
Type IP20
Maximum Vibration 1G according to IEC60068-2-6
Operating Temperature Range -4° to 131°F (-20° to 55°C)
Storage Temperature Range -40° to 158°F (-40° to 70°C)
Maximum Humidity 90% (Relative, non-condensing)
Vibration 0.075mm amplitude; 1.0g acceleration
Weight 10-point: 230g; 8-point:190g; 20-point: 345g
Agency Approvals cUL , CE, UL |
|
|
Discrete Inputs
Current
consumption
4mA @12VDC
3.2mA @24VDC
1.3mA @100-240VAC
Input Signal ”OFF” Threshold
12VDC: < 2.5VDC; 24VDC: < 5VDC;
110/220VAC: < 40VAC
Input Signal ”ON” Threshold
12VDC: > 7.5VDC; 24VDC: > 15VDC;
110/220VAC: > 79VAC
DC
Inputs:
Transistor
Type 3-wire PNP Sensor compatible
High Speed Input frequency 1kHz
Standard Input frequency < 40 Hz
AC
Inputs
Input On delay DC: 5ms; 240VAC: 50ms; 120VAC: 90ms
Input Off Delay DC: 3ms; 240VAC: 50ms; 120VAC: 90ms
Required protection Inverse voltage protection required
Analog Inputs
Resolution 10 bit. Acceptable Input Range
Base module: Analog input: 0-10VDC voltage,
24VDCwhen used as discrete input
Expansion module: Analog input: 0-10VDC voltage or 0-20mA current
Input Signal ”OFF” Threshold < 5VDC (as 24VDC discrete input)
Input Signal ”ON” Threshold > 9.8VDC (as 24VDC discrete input)
Isolation None, Short circuit protection Yes
Total
number available:
Base module: A01-A04, Expansion module: A05-A08
Temperature Input (4PT Expansion Module)
Sensor Type 3-wire PT100
Temperature input range -100°C - 600°C
Resolution 3.5°C
Relay
Outputs
Contact material Ag Alloy
Current rating 10A
HP rating 1/3HP@120V 1/2HP @250V
Maximum Load Resistive: 8A/point; Inductive: 4A/point
Maximum operating time 15ms (normal condition)
Life expectancy (rated load) 100k operations
Minimum load 16.7mA
Transistor Outputs
Pulse
Outputs 1 PWM and 1 PWM or Pulse Output
PWM max. output frequency 0.5kHz (1ms on,1ms off)
Standard max. output frequency 100Hz
Voltage specification 10-28.8VDC, Current capacity 1A
Maximum Load Resistive: 0.5A/point; Inductive: 0.3A/point
Minimum Load 0.2mA
Analog Outputs (2AO Expansion Module)
Analog output range 0V–10V (load > 500 ohm), 0-20mA (load < 500 ohm)
Resolution 10-bit, Full scale accuracy 2.5%
Communication Options
Built-in RS485 Communication (Special Order ED2 units only)
Modbus-RTU, Master/Slave mode, 4800-115.2kb,
supports Modbus function codes 1, 3, 5, 6, 16
Wireless I/O Factory and
Field Systems
DataLink Link up to 3 SG2-20Vx-x units (1-master, 2-slaves) at 38.4kb
Remote-I/O Link up to 8 Remote-I/O slave units to 1-master unit at 8.4kb
Dimensions

|